STP Plants

STP Plants

In INDION FMR, raw sewage enters from the top of the tank. In the aeration zone, air is introduced at the bottom of the tank through fine bubble diffusers. The media gets suspended due to the turbulence created by the air. Bacteria required for oxidation of the organic matter get attached to the media and some are suspended in the tank. After oxidation, the bacteria grow in number and need to be separated from the aeration tank liquor.

The lamella section inside the setting zone helps for clarification and separation of biomass (sludge) and clear water overflow into the chlorine contact tank.

Lamella plates help in increasing the setting area and removing the particles effectively in a smaller plant area. In the chlorine contact tank, sodium hypochlorite (NaOCI) is added to disinfect the clarified sewage.

Baffle plates are provided to increase contact time of treated sewage with chlorine.

Valves are used for sludge removal as well as MLSS (mother liquor suspended solids) adjustment.

The chlorinated, treated sewage then flows out of INDION FMR either for further treatment or for disposal.

Features

  • Single tank design
  • 1/3 space of conventional sewage treatment plant
  • Uses high porosity moving media for bacteria to grow
  • Useful for modification/ capacity extension of existing sewage treatment plant

Advantage

  • Minimum land usage
  • Minimum power & chemical requirement
  • Low operating cost

Application

IINDION FMR deliver treated water to meet local discharge norms and be used as decentralized compact sewage treatment plant for housing complexes, hotels commercial complexes, industries and rural communities. The treated water can be used for gardening, toilet flushing and other law end application

Treated water quality (Domestic Effluent)

Sample After INDION FMR After Tertiary Treatment
BOD 30ppm 5ppm
COD 100ppm 20ppm
Total suspended solid <30ppm <5ppm
Oil & grease <10 <10

The INDION FMR is also suitable for industries effluent piloting may be required to establish sizing and to obtained the treated water characteristics

Technical specification

Model Capacity m3/d Dimensions(in mm) Material of construction
FMR-50 50 4000(I)x2130(w)x2200(h) MSAZP
FMR-100 100 6880(I)x2130(w)x2200(h) MSAZP
FMR-150 150 9280(I)x2130(w)x2200(h) MSAZP
FMR-200 200 11420(I)x2130(w)x2200(h) MSAZP
FMR-250 250 11350(I)x2250(w)x3000(h) MSAZP
FMR-100 100 8000(I)x2500(w)x3500(h) civil
FMR-150 150 8000(I)x2500(w)x3500(h) civil
FMR-200 200 8900(I)x3000(w)x3500(h) civil
FMR-300 300 9100(I)x4000(w)x3500(h) civil
FMR-400 400 10500(I)x5000(w)x3500(h) civil
FMR-500 500 12600(I)x6000(w)x4150(h) civil
FMR-750 750 13200(I)x6600(w)x3500(h) civil
FMR-1000 1000 10400(I)x10000(w)x3500(h) civil
FMR-1500 1500 17000(I)x10500(w)x5000(h) civil
FMR-2000 2000 21000(I)x10500(w)x5000(h) civil
FMR-3000 3000 30000(I)x10500(w)x5000(h) civil
FMR-4000 4000 40000(I)x10500(w)x5000(h) civil
FMR-5000 5000 49000(I)x10500(w)x5000(h) civil
FMR-6000 6000 59000(I)x10500(w)x5000(h) civil